Duct and Pipe Wrap

No Fields Found.

Acoustical Duct and Pipe Wrap for HVAC Noise Control, Sound Barriers, Absorber-Barrier Combination, Mass Loaded Vinyl.

Duct and Pipe Wrap is used to wrap duct work and pipes to dramatically reduce the amount of noise transmitting through the walls or casing of duct work, steel or PVC piping, valves, sheet metal enclosures, plenums, HVAC units, and fans.

Pipe & duct lagging is easy to cut, trim and install on any site and is ideal for industrial and residential noise alike. Simply wrap this acoustical pipe barrier around any cylinder containing noisy air or liquid flow, and tape the seams shut: you will see 15 to 20-decibel level drop in unwanted noise.Size: 54″ X 30’ 1″ thick.

Duct Lagging Features
  • STC ratings fo 26-30
  • Easy to cut and install
  • Accepts matching tape
  • Good corrosion resistance
  • Passes FMVSS 302, UL-94
  • High & Low-Temperature Applications
  • Quilted fiberglass decoupler available

Installation Instructions:  Use tape or clamps to affix the duct lagging material around the circumference of your ductwork or piping. Ask us about a mylar matching tape available to disguise the seams. This is sold in 54″ X 30 ft. roles as an add-on product to the duct wrap. Simply wrap standard pipes or vents with this material. Cut to fit and wrap with matching tape. Custom wrap sizing is available upon request. Size: 4’ X 4’ standard.

ANC-WB21

Acoustical lagging is the same product as above with a one-inch thick quilted fiberglass insulation bonded to the back of the barrier. This quilted fiberglass layer acts as a decoupler/sound absorber to improve overall noise reduction performance, as well as to offer thermal insulation (R-value = 5_. This version allows one-stop installation of the acoustical/thermal insulation layer and noise barrier.
Learn more

ANC-WBV – Wrap Barrier

This lagging is loaded vinyl noise barrier featuring a reinforced-foil facing (aluminum faced mylar) which readily accepts a matching tape. It is supplied in 4′ wide rolls, 30′ or 60′ long. Often specified or used when the duct or pipe is already wrapped with standard insulation.
Learn more

ANC-WB42

This lagging is the same product as above except with a two-inch thick quilted fiberglass decoupler/absorber. This increases noise reduction performance even higher, especially for low-frequency noise problems. This version also improves the R-value to 9.
Learn more

Duct Lagging Features

  • STC ratings fo 26-30
  • Easy to cut and install
  • Accepts matching tape
  • Good corrosion resistance
  • Passes FMVSS 302, UL-94
  • High & Low-Temperature Applications
  • Quilted fiberglass decoupler available

Installation Instructions:  Use tape or clamps to affix the duct lagging material around the circumference of your ductwork or piping. Ask us about a mylar matching tape available to disguise the seams. This is sold in 54″ X 30 ft. roles as an add-on product to the duct wrap. Simply wrap standard pipes or vents with this material. Cut to fit and wrap with matching tape. Custom wrap sizing is available upon request. Size: 4’ X 4’ standard.

FREQUENCY (Hz)
125
250
500
1K
2K
4K
STC
Acoustical Pipe
Acoustical Pipe
Acoustical Pipe
Acoustical Pipe
Acoustical Pipe
Acoustical Pipe
Acoustical Pipe
ANC-WBV 15 18 22 27 32 37 27
ANC-W21 18 18 23 30 39 46 29
ANC-W42 19 20 23 33 44 53 30
PER ASTM:E90
Physical Properties of Components
Product Weight Thickness Service Temperature Tensile  Strength Tear Strength Elongation “R” Factor
Barrier
ANC-WBV 1 lb. PSF .090″ Norm -10º to + 180ºF 400 PSI 72 40%
Decoupler/Absorber
ANC-W21 2 lb. PSF 1″ Norm -20º to + 350ºF 4.0
ANC-W42 4 lb. PSF 2″ Norm -20º to + 350ºF 8.0
Acoustical Pipe & Duct Lagging Flammability Properties
Wrap Barrier UL94: Meets V0    FMVSS-302: Pass
ANC-W21
ANC-W42
ASTM E-84
“Surface Burning Characteristics of Building Materials”;
Meets Class A Rating: Flame Spread Index 12.5 :
Smoke Density Index 19.5

Wrap Barrier - Acoustic Material for residential acoustics or commerical acoustic applications

Acoustical Data:

 

Acoustical Materials:

 

 

Installations

ANC-WB21 & ANC-WB22

Case Study

Northwest Natural Gas Company needs to isolate noise disturbing surrounding farms & residential areas… Read More

Lockheed Martin Missiles & Fire needs to drop equipment noise traveling through pipes to within OSHA guidelines.. Read More

 

Acoustic Applications
  • Exposed Duct work
  • Piping
  • HVAC Systems
  • Blowers
  • Residential
  • Heat Exchanges
  • Valves
Physical Properties
  • 4′ x 30′ rolls. Custom fittings available upon request.
  • Thickness 1″
  • Flammability Passes UL-94V
  • Temperature
  • Heat resistant option to 550OF
  • Safety
  • Non lead
  • Weather
  • Corrosion resistant

The product line is furnished in rolls and is available in three basic styles for quick and easy installation.